THW wire 4 sq.mm (60227 IEC 01) is a single-core PVC-insulated copper building wire to TIS 11 Part 3-2553, rated 450/750 V and 28 A in conduit (single-phase, 40°C). Common for water heaters, small air conditioners and high-power outlets. Yazaki and BCC in 100 m rolls or cut by the metre. Check today's price and order with delivery at OneStockHome.
Brands
List of all THW Wire 4 sq.mm products



























Questions
THW wire 4 sq.mm (60227 IEC 01) is a single-core PVC-insulated copper building wire to TIS 11 Part 3-2553, rated 450/750 V with a 70°C maximum conductor temperature. The conductor is solid or stranded copper. It is common for water heaters, small air conditioners and high-power outlets.
How many amps can THW 4 sq.mm carry?
THW 4 sq.mm carries 28 A in conduit on a single-phase circuit, 24 A on three-phase, and 37 A in free air on insulators, at 40°C ambient (Thai Yazaki catalogue, TIS 11 Part 3-2553). Ratings drop when several circuits share a conduit or the run is hot, so let an electrician or engineer size each circuit and breaker for the real load.
THW 4 sq.mm specifications
Spec | THW wire 4 sq.mm |
|---|---|
Conductor | solid or stranded copper |
Insulation thickness | 0.8 mm |
Max. overall diameter | 4.6 mm |
Max. conductor resistance at 20°C | 4.61 ohm/km |
Current in free air (40°C) | 37 A |
Current in conduit, single-phase (40°C) | 28 A |
Current in conduit, three-phase (40°C) | 24 A |
Approx. weight | 5.5 kg per 100 m |
THW 4 sq.mm price today
Item (black) | Today's price |
|---|---|
Yazaki, 100 m roll | |
BCC, 100 m roll | |
Yazaki, cut to length (min. 10 m) |
OneStockHome sells THW 4 sq.mm from Yazaki and BCC in 100 m rolls, or cut by the metre (min. 10 m) when you need less than a roll. Colours: black, white, red, yellow, blue, brown, grey, green/yellow, green. Prices in the table update from our system every day.
FAQ
How long is a roll of THW 4?
100 m, about 5.5 kg per roll. For shorter runs, buy it cut by the metre (min. 10 m).
Can THW wire be buried?
No. THW runs in conduit or on insulators in dry locations. Never bury it directly or in a conduit that holds water; for underground or wet outdoor runs use a sheathed cable such as NYY.
THW 4 vs VAF: what is the difference?
THW is single-core with insulation only, so it must run in conduit. VAF is a flat 2- or 3-core cable with an outer sheath that can be clipped to a wall, but it carries less current at the same size.
Nearby sizes
Other THW sizes: THW 1.5 sq.mm THW 2.5 sq.mm THW 6 sq.mm THW 10 sq.mm or see every size with the full table on the THW wire page.